Commutation Failure Analysis and Prevention of UHVDC System With Hierarchical Connection Considering Voltage Harmonics
- 2 November 2021
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 37 (4) , 3142-3154
Abstract
Although the harmonics interaction plays a vital role in causing commutation failure (CF) in an ultra HVDC (UHVDC) system with hierarchical connection, it has not been sufficiently considered in previous work. In this paper, the electric interaction among the inverter valves of the UHVDC system with hierarchical connection during receiving system fault transient process is demonstrated. Moreover, the mechanism of CFs in UHVDC system with hierarchical connection is also investigated via the analysis of harmonics interaction. After the AC fault occurs, the appearance processes of the local commutation failure (LCF) and concurrent commutation failure (CCF) are divided into several stages and interpreted by schematic diagrams. And the characteristics of each stage are also concluded. In addition, a coordinated CF prevention scheme based on harmonics and DC current detection is proposed to mitigate the CFs in UHVDC system with hierarchical connection. Finally, the effectiveness of the proposed scheme is verified via a $\pm 1100$ kV UHVDC transmission system under various short circuit ratio values and AC-side coupling strengths.Keywords
Funding Information
- National Natural Science Foundation of China (52022035)
This publication has 24 references indexed in Scilit:
- Power stability analysis of UHVDC systems hierarchically connected to AC systemsElectric Power Systems Research, 2018
- Commutation Failure Elimination of LCC HVDC Systems Using Thyristor-Based Controllable CapacitorsIEEE Transactions on Power Delivery, 2017
- Optimal Reliability Allocation of ±800 kV Ultra HVDC Transmission SystemsIEEE Transactions on Power Delivery, 2017
- Fast Evaluation of Commutation Failure Risk in Multi-Infeed HVDC SystemsIEEE Transactions on Power Systems, 2017
- Decreasing the frequency of HVDC commutation failures caused by harmonicsIET Power Electronics, 2017
- An Evolutional Line-Commutated Converter Integrated With Thyristor-Based Full-Bridge Module to Mitigate the Commutation FailureIEEE Transactions on Power Electronics, 2016
- Practical Passive Filter Designs2015
- Commutation Failure Analysis in Multi-Infeed HVDC SystemsIEEE Transactions on Power Delivery, 2010
- HVDC Protection2009
- A novel method to mitigate commutation failures in HVDC systems2002