Phenomena and Mechanism Analysis on Overvoltages Caused by 40.5-kV Vacuum Circuit Breakers Switching Off Shunt Reactors
Authors:
- 8 August 2011
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 26 (4) , 2102-2110
Abstract
In view of frequent and severe overvoltage failures of 40.5-kV vacuum circuit breakers (CBs) while switching off the shunt reactors in the 35-kV distribution systems in China, a series of field tests was carried out to determine the mechanism of this kind of disruption. The transient process and phenomena were analyzed and summarized based on the overvoltage waveforms obtained from the field tests. The experimental results indicated that the probability of reignition is greater for a 40.5-kV CB than in a 12 kV one. The interphase overvoltage was especially critical. The causes of severe overvoltages were analyzed, and it was indicated that the difference of CBs, multireignitions by the interphase coupling, and the different application conditions were the main effect factors. In addition, some suggestions were given.Keywords
This publication has 7 references indexed in Scilit:
- Investigations of prestriking and current chopping in medium voltage SF/sub 6/ rotating arc and vacuum switchgearIEEE Transactions on Power Delivery, 1989
- Voltage escalation in vacuum switching operationsIEEE Transactions on Power Delivery, 1988
- Surge Limiters for Vacuum Circuit Breaker SwitchgearIEEE Transactions on Power Delivery, 1987
- Overvoltage phenomena associated with virtual current chopping in three phase circuitsIEEE Transactions on Power Apparatus and Systems, 1975
- Extensive field measurements support new approach to protection of arc furnace transformers against switching transientsIEEE Transactions on Power Apparatus and Systems, 1975
- Protection of Motor from Switching Surge by Vacuum SwitchIEEE Transactions on Power Apparatus and Systems, 1974
- Three-Phase Simultaneous Interruption in Interrupting Inductive Current Using Vaccum SwitchesIEEE Transactions on Power Apparatus and Systems, 1974