Condensation Risk Due to Variations in Airtightness and Thermal Insulation of an Office Building in Warm and Wet Climate
Open Access
Abstract
Condensation in a building encourages microbial growth, which can have an adverse effect on the health of occupants. Furthermore, it induces the deterioration of the building. To prevent problems caused by condensation, from the design step of a building, predictions of the spatial, temporal and causation for condensation occurrences are necessary. By using TRNSYS simulation coupled with TRNFLOW, condensation assessment of an entire office building in Tokyo, Japan, was conducted throughout the year, including when the air-conditioning system was not operated, by considering the absorption-desorption properties of the building materials and papers in the office and the airflow within the entire building. It was found that most of the condensation occurred during winter and was observed mainly in the non-air-conditioned core parts, especially the topmost floor. Additional analyses, which identified the effect of variations in the thermal insulation of the external walls, roof and windows and the airtightness of the windows on condensation, showed that the lower airtightness of windows resulted in decreased condensation risks, and condensation within the building was suppressed completely when the thermal insulation material thickness of the external walls was greater than 75 mm, that of the roof was greater than 105 mm and the windows had triple float glass.Keywords
This publication has 29 references indexed in Scilit:
- Risk factors in heating, ventilating, and air-conditioning systems for occupant symptoms in US office buildings: the US EPA BASE studyIndoor Air, 2008
- Meta-analyses of the associations of respiratory health effects with dampness and mold in homesIndoor Air, 2007
- Creating Mold-Free Buildings: A Key to Avoiding Health Effects of Indoor MoldsArchives of Environmental Health: An International Journal, 2003
- Survival of bacterial and mold spores in air filter mediaAtmospheric Environment, 2001
- Relative humidity in the interior of concrete exposed to natural and artificial weatheringCement and Concrete Research, 1999
- The Influence of House Characteristics in a Canadian Community on Microbiological ContaminationIndoor Air, 1998
- Water Condensation Promotes Fungal Growth In Ventilation DuctsIndoor Air, 1993
- SICK BUILDING SYNDROME: A STUDY OF 4373 OFFICE WORKERSAnnals of Occupational Hygiene, 1987
- Condensation Effects in a Fibrous Insulation SlabJournal of Heat Transfer, 1986
- Condensation and mould growth in dwellings—parametric and field studyBuilding and Environment, 1984