High impedance arcing fault detection in MV networks using discrete wavelet transform and Artificial Neural Networks
Authors:
- 1 December 2012
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 089-098
Abstract
Arcing faults in transmission networks are caused when a current carrying conductor makes an unwanted electrical contact with ground or is temporarily short circuited with another current carrying conductor through a high impedance medium. High impedance arcing faults restricts the flow of current below the detection level of the protective devices and hence cannot be detected by conventional relays. In this paper a new method is proposed for the detection of arcing faults due to leaning trees in medium voltage (MV) networks. Firstly, an arc model is developed in order to reproduce the fault circumstances. Then based on a fault detection algorithm the fault features are extracted using a signal processing technique called Discrete Wavelet Transform (DWT).The proposed algorithm is implemented in a simple MV network to identify the faulty phase and in a feeder network to identify both the faulty phase and feeder. Further the results obtained using DWT is validated with the help of Artificial Neural Networks (ANN).The results obtained above validate the effectiveness of the proposed methodology.Keywords
This publication has 8 references indexed in Scilit:
- High impedance fault detection methodology using wavelet transform and artificial neural networksElectric Power Systems Research, 2011
- Approaches in High Impedance Fault Detection - A Chronological ReviewAdvances in Electrical and Computer Engineering, 2010
- DWT-Based Investigation of phase currents for Detecting High Impedance Faults Due to Leaning Trees in Unearthed MV Networks2007 IEEE Power Engineering Society General Meeting, 2007
- Universal Arc Representation Using EMTPIEEE Transactions on Power Delivery, 2005
- An Improved Arc Model Before Current Zero Based on the Combined Mayr and Cassie Arc ModelsIEEE Transactions on Power Delivery, 2005
- Attenuation characteristics of high rate home-networking PLC signalsIEEE Transactions on Power Delivery, 2002
- An improved Mayr-type arc model based on current-zero measurements [circuit breakers]IEEE Transactions on Power Delivery, 2000
- Wavelets and electromagnetic power system transientsIEEE Transactions on Power Delivery, 1996