Marine Power Distribution System Fault Location Using a Portable Injection Unit
Authors:
- 31 October 2014
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 30 (2) , 818-826
Abstract
A portable injection unit for active impedance estimation (AIE) is built and tested in a dc zonal marine power distribution system to provide useful information for system protection and restoration. The portable unit generates current “spikes” and injects them into the system once short-circuit faults are detected (by measuring the system voltage drop). The faulted system impedance can be estimated by AIE and comparing the estimated impedance with the precalibrated value, the fault location can be determined. The proposed method does not rely on system fault transient information or communication from the remote-end measurement and offers fast and accurate fault location in dc marine distribution systems. The proposed method has been tested and validated on a 750-V, 2-MW twin bus dc commercial test facility with the system de-energized and energized.Keywords
This publication has 25 references indexed in Scilit:
- Fold back current control and admittance protection scheme for a distribution network containing distributed generatorsIET Generation, Transmission & Distribution, 2010
- An Adaptive PMU-based Fault Location Estimation System with a Fault-Tolerance and Load-Balancing Communication Network2007
- A Two-terminal Fault Location Approach Based on Unsynchronized Phasors2006
- System reconfiguration on shipboard DC zonal electrical system2005
- Impedance Measurement for Improved Power Quality—Part 1: The Measurement TechniqueIEEE Transactions on Power Delivery, 2004
- Impedance Measurement for Improved Power Quality—Part 2: A New Technique for Stand-Alone Active Shunt Filter ControlIEEE Transactions on Power Delivery, 2004
- Single ended travelling wave fault location scheme based on wavelet analysis2004
- A new type of differential feeder protection relay using the Global Positioning System for data synchronizationIEEE Transactions on Power Delivery, 1997
- Accurate fault location technique for power transmission linesIEE Proceedings C Generation, Transmission and Distribution, 1990
- Optimal coordination of directional overcurrent relays in interconnected power systemsIEEE Transactions on Power Delivery, 1988