Effect of inverted T arrangement on AC pollution flashover characteristics of insulator strings
Authors:
Open Access
- 1 June 2019
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in High Voltage
- Vol. 4 (2) , 97-104
Abstract
The arrangement of insulator strings has an effect on its pollution flashover characteristics. A new arrangement of insulator strings, inverted T‐type arrangement, is proposed in this study. The electric field distribution is simulated and the pollution flashover characteristics are tested in an artificial climate chamber. The test results indicate that the inverted T‐type arrangement can greatly improve the flashover voltage of polluted insulator strings, the ‘7 + 2’ inverted T‐type arrangement can increase the flashover voltage of each insulator by 8.5% on average, and the ‘3 + 3’ inverted T‐type arrangement can increase the flashover voltage of each insulator by 13.4%. The discharge process is different from that of the normal suspension string when the insulator string is inverted T‐shaped, i.e. a local arc is produced at the low voltage end of the insulator string and develops downward along the suspension part. While as for the horizontal tension string parts, it is difficult to generate arc during discharge development.Keywords
Funding Information
- National Natural Science Foundation of China (51637002)
This publication has 2 references indexed in Scilit:
- A review of finite element open boundary techniques for static and quasi-static electromagnetic field problemsIEEE Transactions on Magnetics, 1997
- Performance of Contaminated Insulators Tested from 200 Kv to 1000 Kv DCIEEE Transactions on Electrical Insulation, 1981