Numerical simulations of bridging phenomena in contaminated transformer oil
Authors:
- 1 October 2012
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- No. 00849162,p. 383-386
Abstract
Experiments were carried out on transformer oil contaminated by cellulose fibre. After the high voltage was applied to the electrodes, the pressboard particles accumulated in the highest electric field region and eventually formed a bridge. We have developed a mathematical model to simulate the bridging dynamics. The dielectrophoretic and drag forces are considered for simulation of the particles motion and accumulation. The predicted bridge formation rate and the conduction current between the electrodes showed similar trend to the experimental results. The model is a successful means of predicting bridge formation phenomenon compared with the experimental data.Keywords
This publication has 6 references indexed in Scilit:
- Pre-breakdown characteristics of contaminated power transformer oil2007
- Mineral insulating oil in transformersIEEE Electrical Insulation Magazine, 1998
- Chemical and mineral composition of dust and its effect on the dielectric constantIEEE Transactions on Geoscience and Remote Sensing, 1995
- Fiber DielectrophoresisAerosol Science and Technology, 1989
- Dielectrophoretic force calculationJournal of Electrostatics, 1979
- The Motion and Precipitation of Suspensoids in Divergent Electric FieldsJournal of Applied Physics, 1951