Evaluation of Electric Field Integral Voltage Measurement Method of Transmission Line Based on Error Transmission and Uncertainty Analysis
Open Access
Abstract
Electric field numerical integration algorithms can realize the non-contact measurement of transmission line voltage effectively. Although there are many electric field numerical integration algorithms, lack of a comprehensive comparison of accuracy and stability among various algorithms results in difficulties in evaluating the measurement results of various algorithms. Therefore, this paper presents the G-L (Gauss–Legendre) algorithm, the I-G-L (improved Gauss–Legendre) algorithm, and the I-G-C (improved Gauss–Chebyshev) algorithm and proposes a unified error propagation model of the derived algorithms to assess the accuracy of each integration method by considering multiple error sources. Moreover, evaluation criteria for the uncertainty of transmission line voltage measurement are proposed to analyze the stability and reliability of these algorithms. A simulation model and experiment platform were then constructed to conduct error propagation and uncertainty analyses. The results show that the G-L algorithm had the highest accuracy and stability in the scheme with five integral nodes, for which the simulation error was 0.603% and the relative uncertainty was 2.130%. The I-G-L algorithm was more applicable due to the smaller number of integral nodes required, yet the algorithm was less stable in achieving the same accuracy as the G-L algorithm. In addition, the I-G-C algorithm was relatively less accurate and stable in voltage measurement.Keywords
Funding Information
- Natural Science Foundation Project of Chongqing, Chongqing Science and Technology Commission (cstc2020jcyj-msxmX0881)
- Special Medical Engineering Project for Basic Scientific Research Business Expenses of Central Colleges and Universities (2020CDJYGRH-1006)
- National Innovation Training Program for College Students of Chongqing University (202010611096)
This publication has 28 references indexed in Scilit:
- Non‐contact voltage measurement of three‐phase overhead transmission line based on electric field inverse calculationIET Generation, Transmission & Distribution, 2018
- Contactless voltage sensor for overhead transmission linesIET Generation, Transmission & Distribution, 2018
- Dual LiNbO3 Crystal-Based Batteryless and Contactless Optical Transient Overvoltage Sensor for Overhead Transmission Line and Substation ApplicationsIEEE Transactions on Industrial Electronics, 2017
- Non-contact measurement of lightning and switching transient overvoltage based on capacitive coupling and pockels effectsElectric Power Systems Research, 2016
- B-Dot and D-Dot Sensors for (Sub)Nanosecond High-Voltage and High-Current Pulse MeasurementsIEEE Sensors Journal, 2016
- Design and Simulation Test of an Open D-Dot Voltage SensorSensors, 2015
- A Differential Self-Integration D-Dot Voltage Sensor and Experimental ResearchIEEE Sensors Journal, 2015
- Contactless Measurement of Substation Busbars Voltages and Waveforms Reconstruction Using Electric Field Sensors and Artificial Neural NetworkIEEE Transactions on Smart Grid, 2014
- Calibration of Electromagnetic Dot Sensor—Part 2: D-Dot ModeIEEE Sensors Journal, 2014
- Accurate voltage measurement by the quadrature methodIEEE Transactions on Power Delivery, 2003