Partial discharge measurement and pattern recognition in gas insulated switchgear
Authors:
- 1 November 2011
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 459-462
Abstract
Gas insulated switchgear (GIS) has been widely used as main switching equipment in the power substation, because it has good insulation and high reliability. However, if the switchgear is with defect or beyond the server life, the ability of the insulation may be degradation. Therefore, the detecting technology and fault diagnostic method on GIS has become more and more importance. In this paper, four common defect types of 15 kV switchgears are established, and a commercial inductive sensor measures the current signal caused by the partial discharge (PD) phenomenon. Next transfer this current signal into 3D PD patterns, through these PD patterns we can find the differences characteristic among these testing models. Finally features extract and pattern recognition based on neural network (NN). This detection could determine types of failure and so assist in utility maintenance.Keywords
This publication has 10 references indexed in Scilit:
- Influence of disconnecting part on propagation properties of PD-induced electromagnetic wave in model gisIEEE Transactions on Dielectrics and Electrical Insulation, 2010
- Detecting characteristics of various type antennas on partial discharge electromagnetic wave radiating through insulating spacer in gas insulated switchgearIEEE Transactions on Dielectrics and Electrical Insulation, 2009
- Artificial recognition system for defective types of transformers by acoustic emissionExpert Systems with Applications, 2009
- Application possibilities of artificial neural networks for recognizing partial discharges measured by the acoustic emission methodIEEE Transactions on Dielectrics and Electrical Insulation, 2009
- Determination of neural-network topology for partial discharge pulse pattern recognitionIEEE Transactions on Neural Networks, 2002
- The influence of dielectric surface charge distribution upon the partial discharge behavior in short air gapsIEEE Transactions on Plasma Science, 2001
- The behavior of water in XLPE and EPR cables and its influence on the electric characteristics of insulationIEEE Transactions on Power Delivery, 1999
- Can fractal features be used for recognizing 3-d partial discharge patternsIEEE Transactions on Dielectrics and Electrical Insulation, 1995
- The use of fractal features for recognition of 3-D discharge patternsIEEE Transactions on Dielectrics and Electrical Insulation, 1995
- Development of detection and diagnostic techniques for partial discharges in GISIEEE Transactions on Power Delivery, 1994