Condition assessment of outdoor porcelain insulator based on dielectric dissipation factor evaluated from non‐linear equivalent circuit
Open Access
- 1 November 2016
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Science, Measurement & Technology
- Vol. 10 (8) , 866-873
Abstract
This study presents a novel technique for estimation of contamination level as well as flashover voltage of outdoor insulators based on dielectric dissipation factor evaluated from the applied sinusoidal excitation and corresponding surface leakage current. Existing literature shows that surface leakage current of insulator is infested with odd harmonics though the applied voltage is sinusoidal in nature. The presence of harmonic contents in leakage current is due to non‐linear characteristics of the insulator surface owing to formation of dry bands. The nonlinear characteristic of the insulator surface depends on its contamination level which in turn affects the corresponding flashover voltage. Therefore, the harmonic configuration in leakage current can be correlated with the contamination level on insulator surface and corresponding flashover voltage. Considering the fact, in this contribution, a non‐linear equivalent circuit of insulator has been proposed based on harmonic components of the leakage current. For each harmonic component of the leakage current flowing through the insulator system, energy lost and energy stored in the system is calculated, which eventually enables to calculate dielectric dissipation factor. The proposed technique is applied for experimental investigation on 11 kV disc porcelain insulator artificially contaminated in the laboratory under controlled environmental conditions.Keywords
This publication has 19 references indexed in Scilit:
- Determining the probability of flashover occurrence in composite insulators by using leakage current harmonic componentsIEEE Transactions on Dielectrics and Electrical Insulation, 2010
- Artificial neural network optimisation methodology for the estimation of the critical flashover voltage on insulatorsIET Science, Measurement & Technology, 2009
- Leakage current characterization for estimating the conditions of non-ceramic insulators’ surfacesElectric Power Systems Research, 2007
- Frequency characteristics of leakage current waveforms of a string of suspension insulatorsIEEE Transactions on Power Delivery, 2005
- Fundamental and low frequency harmonic components of leakage current as a diagnostic tool to study aging of RTV and HTV silicone rubber in salt-fogIEEE Transactions on Dielectrics and Electrical Insulation, 2003
- Frequency characteristics of leakage current waveforms of an artificially polluted suspension insulatorIEEE Transactions on Dielectrics and Electrical Insulation, 2001
- Polymer insulator profiles evaluated in a fog chamberIEEE Transactions on Power Delivery, 1990
- Surface flashover of insulatorsIEEE Transactions on Electrical Insulation, 1989
- AC withstand voltage characteristics of insulator string covered with snowIEEE Transactions on Power Delivery, 1988
- Wind Tunnel Studies of the Insulator Contamination ProcessIEEE Transactions on Electrical Insulation, 1981