Distortion levels on power systems have been continuously growing because of the increasing presence of loads, producing interharmonics as well as harmonics. Because in some loads such as arc furnaces, the interharmonic pollution is remarkable, the traditional power system unbalance indices and different apparent power quantities, in which only harmonic components were considered, create extraordinary errors. This paper proposes a beneficial method for extracting the actual amount of unbalance and the accurate apparent power quantities under nonsinusoidal, unbalanced conditions and in the presence of interharmonic components. In this regard, appropriate unbalance and harmonic distortion factors are defined. First, five case studies are presented to show the validity of the proposed indices. Then, in order to show the practicality of the introduced method, the proposed quality indices are calculated for data acquired through simulation of two typical steel industrial plants with a DC electric arc furnace. The results are compared with cases in which the interharmonic components have been neglected. On the basis of simulation studies, precision of the proposed method is represented, and it is shown that the obtained results are more accurate than those obtained by eliminating the interharmonic components. Copyright © 2012 John Wiley & Sons, Ltd.Keywords
This publication has 12 references indexed in Scilit:
- Comprehensive Definitions for Evaluating Harmonic Distortion and Unbalanced Conditions in Three- and Four-Wire Three-Phase Systems Based on IEEE Standard 1459IEEE Transactions on Power Delivery, 2011
- Interharmonics: Theory and ModelingIEEE Transactions on Power Delivery, 2007
- Signal Processing of Power Quality Disturbances2005
- On the Phase Sequence Characteristics of InterharmonicsIEEE Transactions on Power Delivery, 2005
- A Comparative Study of AC/DC Converters for High-Power DC Arc FurnaceIEEE Transactions on Industrial Electronics, 2005
- Chaos-Based Modeling of DC Arc Furnaces for Power Quality IssuesIEEE Transactions on Power Delivery, 2004
- Desynchronized Processing Technique for Harmonic and Interharmonic AnalysisIEEE Transactions on Power Delivery, 2004
- Summary of IEEE Standard 1459: Definitions for the Measurement of Electric Power Quantities Under Sinusoidal, Nonsinusoidal, Balanced, or Unbalanced ConditionsIEEE Transactions on Industry Applications, 2004
- On the Processing of Harmonics and Interharmonics: Using Hanning Window in Standard FrameworkIEEE Transactions on Power Delivery, 2004
- Evaluating power system unbalance in the presence of harmonic distortionIEEE Transactions on Power Delivery, 2003