Configuration Optimization Model for Data-Center-Park-Integrated Energy Systems under Economic, Reliability, and Environmental Considerations
Open Access
Abstract
The analysis of energy configuration in the planning of data-center-park-integrated energy systems (DCP-IESs) has become an enormous challenge, owing to multi-energy complementarity, energy cascade use, and energy security. In this study, a configuration model of DCP-IESs was established to obtain the economic and low-carbon energy uses of the data centers, based on mixed integer linear programming. In the model, carbon emissions were converted to economic indicators through carbon pricing. Then, the configuration model was modified according to the security of the proposed device switching logic, and the Markov-based reliability estimation method was used to ensure the redundant design of the configuration. Using the new energy configuration method, the DCP-IES configuration scheme could be obtained under economical, low-carbon, and high reliability conditions. A data center park in Shanghai was selected as a case study, and the results are as follows: it will only take 2.88 years for the economics of DCP-IES to reach those of traditional data center energy systems. Additionally, the use of configuration model in DCP-IES would result in a reduction in annual carbon emissions of 39,323 tons, with a power usage effectiveness of 1.388, whereas an increase in reliability results in an increasingly faster increase in the initial investment cost.Keywords
This publication has 37 references indexed in Scilit:
- A review of data centers as prosumers in district energy systems: Renewable energy integration and waste heat reuse for district heatingApplied Energy, 2020
- E-eco: Performance-aware energy-efficient cloud data center orchestrationJournal of Network and Computer Applications, 2017
- Application of separated heat pipe system in data center coolingApplied Thermal Engineering, 2016
- Comparative analysis on operation strategies of CCHP system with cool thermal storage for a data centerApplied Thermal Engineering, 2016
- Optimizing energy consumption for data centersRenewable and Sustainable Energy Reviews, 2016
- Economic feasibility study of a fuel cell-based combined cooling, heating and power system for a data centreEnergy and Buildings, 2016
- Analyzing the Data Center Efficiency by Using PUE to Make Data Centers More Energy Efficient by Reducing the Electrical Consumption and Exploring New StrategiesProcedia Computer Science, 2015
- Performance-controlled server consolidation for virtualized data centers with multi-tier applicationsSustainable Computing: Informatics and Systems, 2014
- Energy-efficient scheduling in multi-core serversComputer Networks, 2014
- Energy efficient virtual machine placement algorithm with balanced and improved resource utilization in a data centerMathematical and Computer Modelling, 2013