Scaling of internal wall temperatures in enclosure fires
Authors:
- 15 December 2014
- journal article
- research article
- Published by SAGE Publications in Journal of Fire Sciences
- Vol. 33 (2) , 113-141
Abstract
Physical scaling is an efficient and cost-effective modeling tool to be used in fire safety engineering. Scaling of internal wall temperatures was investigated in room fire tests in three different scales, that is, full scale (1:1), medium scale (1:2), and small scale (1:3.5). The fire sources were either placed at the center or in the corner of the enclosures. The measured time-dependent internal wall temperatures, incident heat fluxes, and gas temperatures in different scales are compared and analyzed. Test results show that the proposed scaling method is able to scale the internal wall temperatures (temperatures inside the walls) and incident heat fluxes well, especially in medium scale.Keywords
This publication has 23 references indexed in Scilit:
- Position of Maximum Ceiling Temperature in a Tunnel FireFire Technology, 2012
- Using plate thermometer measurements to calculate incident heat radiationJournal of Fire Sciences, 2012
- Scale modeling and numerical simulation of smoke control for rescue stations in long railway tunnelsJournal of Fire Protection Engineering, 2012
- The maximum ceiling gas temperature in a large tunnel fireFire Safety Journal, 2012
- Model scale tunnel fire tests with point extraction ventilationJournal of Fire Protection Engineering, 2011
- Theoretical and Experimental Study of Critical Velocity for Smoke Control in a Tunnel Cross-PassageFire Technology, 2010
- Scale Modeling of the Transient Thermal Response of Insulated Structural Frames Exposed to FireFire Technology, 2007
- Extinction of gas and liquid pool fires with water spraysFire Safety Journal, 2003
- Scaling the interaction of water sprays and flamesFire Safety Journal, 2002
- A robust bidirectional low-velocity probe for flame and fire applicationCombustion and Flame, 1976