Abstract
With the large-scale grid connection of new energy equipment, impedance modelling has become a key method for system stability analysis. Existing research has failed to fully meet the demands of practical engineering applications, with limited analysis of multi-link joint modelling incorporating power loops and feedforward control, as well as investigations into their impedance characteristics and inter-stage coupling effects. Taking the LCL inverter as the subject of study, this paper proposes an impedance modelling method incorporating the power loop, active damping, and voltage feedforward. Models are established in both the dq-domain and sequence-domain, analysing the influence of each control module on impedance characteristics and inter-sequence coupling. Frequency mapping-based disturbance injection is employed for full-band frequency sweeping, with theoretical and simulation results demonstrating high consistency, thereby validating the model's accuracy. Stability analysis demonstrates that time-domain simulations align with model predictions, confirming the model's reliability for stability assessment.Keywords
Funding Information
- National Natural Science Foundation of China (52277005)
This publication has 10 references indexed in Scilit:
- Symmetrical Phase-Locked Loop and Power Control Loop for Grid-Connected InvertersIEEE Transactions on Power Electronics, 2025
- Sequence Impedance Modeling Method for LCL-Type Grid-Connected Inverters Considering Frequency Coupling2024
- Review of Impedance Measurement Methods in New Energy Scenarios2024
- Admittance-Based Stability Analysis of LCL-Type Grid-Connected Inverter Considering AC-Side and AC-DC Frequency Coupling EffectsIEEE Transactions on Power Delivery, 2024
- Equivalence analysis of different sequence impedance modeling methods2023
- Sequence impedance modeling and stability mechanism analysis of three-phase grid-connected inverter considering frequency coupling2022
- Sequence Impedance Modeling and Stability Analysis of Grid-Connected LCL-type Voltage Source Converter Considering Control Delay and the Frequency Coupling Effect of the SPWM Modulator2022
- Impedance modeling and stability analysis of PV grid-connected inverter system considering frequency couplingCSEE Journal of Power and Energy Systems, 2020
- Impedance Modeling and Stability Analysis of Three-phase Grid-connected Inverter with LCL Filter in dq-frame2019
- A Modified Sequence-Domain Impedance Definition and Its Equivalence to the dq-Domain Impedance Definition for the Stability Analysis of AC Power Electronic SystemsIEEE Journal of Emerging and Selected Topics in Power Electronics, 2016