Abstract
Transformer oil is the most widely used dielectric liquid for high voltage insulation. Measurements of the electric field distribution in high voltage pulsed transformer oil are of both practical and theoretical interests. Due to its low Kerr constant, previous electro-optic measurements with transformer oil rely on a technique called ac modulation, which works only for dc steady-state electric field mapping. With the help of a high-sensitivity charge-coupled device, we directly measure the Kerr electro-optic effect between parallel electrodes in transformer oil stressed by high voltage pulses. This work aims at demonstrating the reliability and evaluating the sensitivity of the measurements for three cases with identical electrodes: space-charge free, uniform electric field in the mid-region of the gap; space-charge free, non-uniform fringing electric field; and space charge distorted electric field in the mid-region of the gap. Future directions to improve accuracy by identifying and handling various sources of error and noise are suggested.

This publication has 6 references indexed in Scilit: