Determination of flicker contributions based on synchronised measurements of rapid RMS changes
Open Access
- 1 October 2017
- journal article
- Published by Institution of Engineering and Technology (IET) in CIRED - Open Access Proceedings Journal
- Vol. 2017 (1) , 585-588
Abstract
This study proposes a method for the determination of flicker contribution based on synchronised measurements of root mean square (RMS) voltages and currents. The advantage of this approach is the avoidance of time aggregation which is present in the analysis based on the short- or long-term flicker coefficient. The applicability of the method is demonstrated using phasor measurement unit measurements from a 50 kV network and compared with the results of an analysis based on instantaneous flicker coefficients.Keywords
This publication has 2 references indexed in Scilit:
- Effect of Transfer Coefficients on MV and LV Flicker LevelsIEEE Transactions on Power Delivery, 2009
- Synchronized Flicker Measurement for Flicker Transfer Evaluation in Power SystemsIEEE Transactions on Power Delivery, 2006