A novel adaptive loss of excitation protection criterion based on steady-state stability limit
Authors:
- 1 December 2013
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- No. 21574839,p. 1-5
Abstract
Among Loss-Of-Excitation (LOE) protections of synchronous generators, the impedance boundary criterion of steady-state stability limit (SSSL) is widely used to distinguish LOE from non-LOE conditions. But this criterion is sensitive to the variation of output active power of synchronous generator, and may mal-operate in external faults, power-swing and other non-LOE conditions. In this paper, a novel adaptive LOE protection criterion with an offset mho element based on SSSL is presented. The new criterion could automatically adapt to the system operating modes and correctly operate in LOE. Combine this criterion with some measures which prevent mal-operation in non-LOE conditions, a new LOE protection scheme is proposed. Simulation results demonstrated the effectiveness of the proposed adaptive LOE protection criterion and scheme.Keywords
This publication has 9 references indexed in Scilit:
- Identification of generator loss‐of‐excitation from power‐swing conditions using a fast pattern classification methodIET Generation, Transmission & Distribution, 2013
- The comparison and analysis for loss of excitation protection schemes in generator protection2012
- Adaptive loss of field protection based on phasor measurements2011
- An Innovative Loss-of-Excitation Protection Based on the Fuzzy Inference MechanismIEEE Transactions on Power Delivery, 2010
- Combined Positional and Boundary Protection for Transmission Lines2009
- Dynamic simulations help improve generator protection2007
- Power System Protection1998
- Loss of excitation protection for modern synchronous generatorsIEEE Transactions on Power Apparatus and Systems, 1975
- A New Loss-of-Excitation Relay for Synchronous GeneratorsTransactions of the American Institute of Electrical Engineers, 1949