FDTD Simulation of Insulator Voltages at a Lightning-Struck Tower Considering Ground-Wire Corona
- 24 May 2013
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 28 (3) , 1635-1642
Abstract
In this paper, a simplified model of corona discharge for the finite-difference time-domain (FDTD) computations has been applied to the analysis of transient voltages across insulators of a transmission line struck by lightning. In the simulation, three 60-m towers, separated by 200 m, with one overhead ground wire and three-phase conductors are employed. The progression of corona streamers from the ground wire is represented as the radial expansion of cylindrical conducting region around the wire. On the basis of the computed results, the effect of corona discharge at the ground wire on transient insulator voltages is examined. The insulator voltages are reduced by corona discharge on the ground wire. The reduction of insulator-voltage peak due to the ground-wire corona is not very significant: the upper-, middle-, and lower-phase-voltage peaks are reduced by 15, 14, and 13% for a positive stroke with 50-kA-peak and 3-μs-risetime current, and those for the negative stroke with the same current waveform parameters are reduced by 10, 9, and 8%, respectively.Keywords
This publication has 15 references indexed in Scilit:
- FDTD Simulation of Lightning Surges on Overhead Wires in the Presence of Corona DischargeIEEE Transactions on Electromagnetic Compatibility, 2012
- A Numerical Simulation of Transient Electromagnetic Fields for Obtaining the Step Response of a Transmission Tower Using the FDTD MethodIEEE Transactions on Power Delivery, 2008
- Revision, Extension, and Validation of Jordan's Formula to Calculate the Surge Impedance of Vertical ConductorsIEEE Transactions on Electromagnetic Compatibility, 2006
- On the transmission line model for lightning return stroke representationGeophysical Research Letters, 2003
- Charge-voltage curves of surge corona on transmission lines: two measurement methodsIEEE Transactions on Power Delivery, 2003
- Thin wire representation in finite difference time domain surge simulationIEEE Transactions on Power Delivery, 2002
- Numerical electromagnetic field analysis on lightning surge response of tower with shield wireIEEE Transactions on Power Delivery, 2000
- An efficient procedure for the implementation of corona models in electromagnetic transients programsIEEE Transactions on Power Delivery, 1994
- Theoretical Evaluation of Peek's LawIEEE Transactions on Industry Applications, 1984
- High-Voltage Impulse Tests on Transmission Lines [includes discussion]Transactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems, 1954