Cumulative deformation analysis of transformer winding under short-circuit fault using 3-D FEM
Authors:
- 1 November 2015
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 370-371
Abstract
It is inevitable for power transformers to suffer multiple impacts of short-circuit (SC) current and huge dynamic electromagnetic force in service which may cause large elastic and plastic deformations. Under the SC fault, the distribution of flux leakage and the amplitude of electromagnetic force may be disturbed by deformations. This paper analyzes the cumulative strain-stress characteristics inner of the transformer windings by using the coupled electromagnetic-structural analysis solution. The dynamic electromagnetic force, mechanical stress, and plastic deformation are calculated by using 3-D finite element method (FEM). An example of two-winding, 110 kV transformer is simulated. It is founded that an initial and little deformation of windings can also influence the distribution of flux density, which may enlarge the electromagnetic force applied in the windings. The cumulative model and results in this paper may be useful to study the prediction of winding deformation state.Keywords
This publication has 5 references indexed in Scilit:
- Effect of Geometry Change on the Deformation in C-Shaped Armatures Through 3-D Magnetic-Structural Coupling FE AnalysisIEEE Transactions on Plasma Science, 2013
- Experimental Verification and Finite Element Analysis of Short-Circuit Electromagnetic Force for Dry-Type TransformerIEEE Transactions on Magnetics, 2012
- FE-Based Modeling of Single-Phase Distribution Transformers With Winding Short Circuit FaultsIEEE Transactions on Magnetics, 2007
- Comparison of different force calculation methods in 3D finite element modellingIEEE Transactions on Magnetics, 1994
- Mechanical strength of power transformers in serviceProceedings of the IEE - Part A: Power Engineering, 1957