PMU Angle Deviation Detection and Correction Using Line Reactive Power Measurements
- 15 June 2022
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Systems
- Vol. 38 (3) , 2679-2689
Abstract
The phase angle difference between local voltage and current phasors from the phasor measurement unit (PMU), which is defined as the power factor angle (PFA), is sensitive to voltage and current transformer errors and signal transmission delay. This paper proposes a robust PFA deviation (PFAD) detection and correction method using transmission line (TL) reactive power. Specifically, the root cause of PFAD and its influence on the calculated power measurements from PMU are analyzed. Then, an expression for TL reactive power loss independent of phase angle is derived. This allows the development of a detection method for PFAD that takes into account PMU measurement errors and TL parameter deviation. A method for estimating PFAD is also proposed to correct the PFAD at both ends of a transmission line. Simulation results using both simulated and field data demonstrate the effectiveness and robustness of the proposed method.Keywords
Funding Information
- Science and technology Project of State Grid Corporation of China (5108-2020190227A-0, -0-00)
This publication has 31 references indexed in Scilit:
- Detection and Correction of Systematic Errors in Instrument Transformers Along With Line Parameter Estimation Using PMU DataIEEE Transactions on Power Systems, 2016
- Online Detection of Stealthy False Data Injection Attacks in Power System State EstimationIEEE Transactions on Smart Grid, 2016
- Impact of GPS Signal Loss and Its Mitigation in Power System Synchronized Measurement DevicesIEEE Transactions on Smart Grid, 2016
- The Impact of Time Synchronization Deviation on the Performance of Synchrophasor Measurements and Wide Area Damping ControlIEEE Transactions on Smart Grid, 2016
- Online Calibration of Voltage Transformers Using Synchrophasor MeasurementsIEEE Transactions on Power Delivery, 2015
- Power System Real-Time Monitoring by Using PMU-Based Robust State Estimation MethodIEEE Transactions on Smart Grid, 2015
- False data injection attacks against state estimation in electric power gridsACM Transactions on Information and System Security, 2011
- A Phasor-Data-Based State Estimator Incorporating Phase Bias CorrectionIEEE Transactions on Power Systems, 2010
- Synchronized Phasor Measurement Applications in Power SystemsIEEE Transactions on Smart Grid, 2010
- Parameter Sensitivity and Measurement Error Propagation in Torque Estimation Algorithms for Induction Machines2006