The emerging use of dc power systems places a greater need for dc circuit breakers, an important part of system protection. Unlike with ac, for dc there is no inherent current-zero in the applied power to assist in the current interruption process. In this paper, a passive means to redirect the fault current to force a transient current reversal and a current zero in the switch element is analyzed. Passive inductance and capacitance elements are configured in an H-bridge structure that enables a solid-state thyristor SCR (or other switch element) within the bridge to open and achieve dc circuit breaker action. Time domain analysis with tests of this passive current-reversal H-bridge circuit breaker is presented along with a theoretical basis for breaker designs of this type. Results show this circuit can be designed to exhibit enhanced breaker performance with minimal component size and weight.Keywords
This publication has 17 references indexed in Scilit:
- Successful fault current interruption on DC circuit breakerIET Power Electronics, 2016
- Control strategy of the full-bridge based hybrid DC breaker2015
- HVDC circuit breakers for HVDC grid applications2015
- Design aspects of a medium voltage hybrid DC breaker2014
- A Review on HVDC Circuit Breakers2014
- A DC Arc Model for Series Faults in Low Voltage MicrogridsIEEE Transactions on Smart Grid, 2012
- A fast acting DC solid state fault isolation device (FID) with Si and SiC devices for MVDC distribution system2012
- A New Z-Source DC Circuit BreakerIEEE Transactions on Power Electronics, 2012
- Structure and analysis of the Z-source MVDC breaker2011
- Design and Reliability Analysis of High Power DC Thyristor Breaker2006