Automated parameter derivation for power plant models based on staged tests
Author:
- 1 March 2009
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- p. 1-9
Abstract
This paper describes an approach for automated parameter derivation of models for synchronous generators, their excitation system and the turbine-governor. The methodology is based on performing and collecting data from a series of staged tests (mainly off-line). This data is then used in an automated routine to fit parameters to selected standard model structures. The results of this work have provided some quite significant insight into the process, strengths and weaknesses of field testing and generator model validation.Keywords
This publication has 6 references indexed in Scilit:
- Model Development and Field Testing of a Heavy-Duty Gas-Turbine GeneratorIEEE Transactions on Power Systems, 2008
- A new thermal governor modeling approach in the WECC2004
- New Thermal Governor Model Selection and Validation in the WECCIEEE Transactions on Power Systems, 2004
- Utility experience with gas turbine testing and modeling2002
- Experience with standstill frequency response (SSFR) testing and analysis of salient pole synchronous machinesIEEE Transactions on Energy Conversion, 1999
- Inherent Errors in the Determination of Synchronous-Machine Reactances by TestTransactions of the American Institute of Electrical Engineers, 1945