Lightning Surge Response Of Transmission Towers
Authors:
- 1 September 1983
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Apparatus and Systems
- Vol. PAS-102 (9) , 3232-3242
Abstract
A sensitivity study of HV and EHV lightning performance shows that surge response characteristics of towers and lines are as important as the footing response. Tower travel time has a very large sensitivity for taller double-circuit lines. Existing methods for analysis of tower and line response have considerable uncertainty. This uncertainty is resolved by extensions to travelling- wave analysis combined with experimental verification. New equations for tower surge impedance and tower travel time are proposed to deal with the most common situation of a midspan stroke to the skywire.Keywords
This publication has 7 references indexed in Scilit:
- Lightning Performance of TVA'S 500-kV 161-kV Transmission LinesIEEE Transactions on Power Apparatus and Systems, 1983
- Surge response of transmission towersCanadian Electrical Engineering Journal, 1982
- Wave Propagation on Nonuniform LinesIEEE Transactions on Power Apparatus and Systems, 1982
- Lightning Performance -- I Shielding Failures SimplifiedIEEE Transactions on Power Apparatus and Systems, 1978
- Tower Surge ImpedanceIEEE Transactions on Power Apparatus and Systems, 1969
- Studies of the Surge Response on a Transmission Line TowerIEEE Transactions on Power Apparatus and Systems, 1964
- An Approximate Transient Solution of the Tapered Transmission LineTransactions of the American Institute of Electrical Engineers. Part III: Power Apparatus and Systems, 1957