Evaporator superheat control With one temperature sensor using qualitative system knowledge
Authors:
- 1 June 2012
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- No. 07431619,p. 374-379
Abstract
This paper proposes a novel method for superheat control using only a single temperature sensor at the outlet of the evaporator, while eliminating the need for a pressure sensor. An inner loop controls the outlet temperature and an outer control loop provides a reference set point, which is based on estimation of the evaporation pressure and suitable reference logic. The pressure is approximated as being linear and proportional to the opening degree of the expansion valve. This gain and the reference logic is based on calculation of the variance in the outlet temperature, which have shown to increase at low superheat. The parameters in the proposed controller structure can automatically be chosen based on two open loop tests. Results from tests on two different refrigeration systems indicate that the proposed controller can control the evaporator superheat to a low level giving close to optimal filling of the evaporator, with only one temperature sensor. No a priori model knowledge was used and it is anticipated that the method is applicable on a wide variety of refrigeration systems.Keywords
This publication has 8 references indexed in Scilit:
- Refrigeration Systems and Applications2010
- On reducing evaporator superheat nonlinearity with control architectureInternational Journal of Refrigeration, 2010
- Selecting PID Control Gains for Nonlinear HVAC&R SystemsHVAC&R Research, 2009
- Nonlinear superheat and capacity control of a refrigeration plant2009
- Adaptive superheat control of a refrigeration plant using backstepping2008
- Advanced controller auto-tuning and its application in HVAC systemsControl Engineering Practice, 2000
- A New Pattern Recognition Adaptive Controller with Application to HVAC SystemsAutomatica, 1998
- Multivariable Control of Vapor Compression SystemsHVAC&R Research, 1998