This study employed two ventilation indexes: local mean age of air and air change rate per hour, to investigate wind-induced natural ventilation of 260 wards of a multi-storey hospital building in suburb of Guangzhou using computational fluid dynamics simulations. Using the surface-grid extrusion technique, high-quality hexahedral grid cells were generated for the coupled outdoor and indoor airflow field. Turbulence was solved by the renormalisation group k-ɛ model validated against experimental data with grid independence studies. Homogeneous tracer gas emission was adopted to predict room age of air. The air change rate of cross ventilation and single-sided ventilation can reach 30–160 h−1 and 0.5–7 h−1, respectively. Due to different locations of room openings on the balconies, natural ventilation of a room can be greatly better than its neighbouring room. The wind-induced cross ventilation highly depends on the distance from the room opening to the stagnation point and on the resulting pressure distribution on the target building surface. Furthermore, it is significantly influenced by the upstream buildings, the bent shape of the target building, and the prevailing wind directions. The coupled computational fluid dynamics methodologies with integrated ventilation indexes are useful for assessing the natural ventilation performance in other complex built environments.Keywords
This publication has 60 references indexed in Scilit:
- Ventilation system type, classroom environmental quality and pupils' perceptions and symptomsBuilding and Environment, 2014
- Feedback from human adaptive behavior to neutral temperature in naturally ventilated buildings: Physical and psychological pathsBuilding and Environment, 2013
- Roles of sunlight and natural ventilation for controlling infection: historical and current perspectivesJournal of Hospital Infection, 2013
- Measurement of temperature, relative humidity, concentration distribution and flow field in four typical Chinese commercial kitchensBuilding and Environment, 2012
- Natural ventilation for reducing airborne infection in hospitalsBuilding and Environment, 2010
- Ventilation Control of Indoor Transmission of Airborne Diseases in an Urban CommunityIndoor and Built Environment, 2009
- Impact of Artemisinin-Based Combination Therapy and Insecticide-Treated Nets on Malaria Burden in ZanzibarPLOS Medicine, 2007
- Role of ventilation in airborne transmission of infectious agents in the built environment ? a multidisciplinary systematic reviewIndoor Air, 2007
- Evidence of Airborne Transmission of the Severe Acute Respiratory Syndrome VirusNew England Journal of Medicine, 2004
- AIRBORNE SPREAD OF MEASLES IN A SUBURBAN ELEMENTARY SCHOOLAmerican Journal of Epidemiology, 1978