Voltage Ride-Through Capability Verification of Wind Turbines With Fully-Rated Converters Using Reachability Analysis
Authors:
- 1 June 2014
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Energy Conversion
- Vol. 29 (2) , 392-405
Abstract
Wind turbines are required to meet grid interconnection codes for voltage ride-through, which mandate that they should not disconnect during a specified range of grid disturbances. One of the tasks of a turbine's design verification process is to ensure that it will be able to withstand any such event. This paper sets forth a powerful computational technique for design verification of Type-4 permanent-magnet synchronous generator-based turbines with fully-rated grid-side converters. The proposed method can provide assurance as to whether the currents and voltages will remain within acceptable bounds. To this end, reachability theory is employed to find sets that enclose all possible trajectories for the system states caused by a given set of unknown-but-bounded disturbances. The computation of the reachable sets is carried out by using on-the-fly linearization of the nonlinear system dynamics, zonotopes, and interval analysis.Keywords
Funding Information
- Power Systems Engineering Research Center
This publication has 45 references indexed in Scilit:
- Computing reachable sets of hybrid systems using a combination of zonotopes and polytopesNonlinear Analysis: Hybrid Systems, 2010
- A review of grid code technical requirements for wind farmsIET Renewable Power Generation, 2009
- Wind-Turbine Fault Ride-Through EnhancementIEEE Transactions on Power Systems, 2005
- Ridethrough of Wind Turbines with Doubly-Fed Induction Generator During a Voltage DipIEEE Transactions on Energy Conversion, 2005
- Power System Modeling for Inverse ProblemsIEEE Transactions on Circuits and Systems I: Regular Papers, 2004
- Computational techniques for the verification of hybrid systemsProceedings of the IEEE, 2003
- Computational techniques for hybrid system verificationIEEE Transactions on Automatic Control, 2003
- On Ellipsoidal Techniques for Reachability Analysis. Part I: External ApproximationsOptimization Methods and Software, 2002
- Interval observers for uncertain biological systemsEcological Modelling, 2000
- Characterisation of voltage sags experienced by three-phase adjustable-speed drivesIEEE Transactions on Power Delivery, 1997