A New Noncommunication-Based Protection Scheme for Three-Terminal Transmission Lines Employing Mathematical Morphology-Based Filters
Authors:
- 29 November 2012
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 28 (1) , 347-356
Abstract
In this paper, a new noncommunication-based scheme is presented for the protection of three-terminal transmission lines. Using this scheme, simultaneous operation of circuit breakers (CBs) at all terminals is provided for all internal faults. This scheme can discriminate between external and internal faults based on initiated transients by faults, considering the high-stop filtering property of busbars through modeling their stray capacitances and employing a newly defined mathematical morphology (MM) filter to analyze the captured transients. Moreover, the transients generated by lightning or switching are identified and prohibited to enter the algorithm. The presented scheme has been applied on one of three-terminal lines in Iran's Transmission Grid. The effects of fault resistance, fault inception angle, (internal) fault location, and fault type on the performance of the proposed scheme are evaluated, where the high dependability, accuracy, and speed are verified.Keywords
This publication has 20 references indexed in Scilit:
- High-speed transmission line protection using principal component analysis, a deterministic algorithmIET Generation, Transmission & Distribution, 2011
- A Traveling-Wave-Based Protection Technique Using Wavelet/PCA AnalysisIEEE Transactions on Power Delivery, 2010
- A New Approach Traveling-Wave Distance Protection—Part I: AlgorithmIEEE Transactions on Power Delivery, 2007
- Improved Single-Ended Traveling-Wave Fault- Location Algorithm Based on Experience With Conventional Substation TransducersIEEE Transactions on Power Delivery, 2006
- Study of protection scheme for transmission line based on wavelet transient energyInternational Journal of Electrical Power & Energy Systems, 2006
- Transient positional protection of transmission lines using complex wavelets analysisIEEE Transactions on Power Delivery, 2003
- A travelling wave distance protection using principal component analysisInternational Journal of Electrical Power & Energy Systems, 2003
- Positional protection of transmission line using fault generated high frequency transient signalsIEEE Transactions on Power Delivery, 2000
- A new non-communication protection technique for transmission linesIEEE Transactions on Power Delivery, 1998
- Non-unit protection technique for EHV transmission systems based on fault-generated noise. Part 2: signal processingIEE Proceedings - Generation, Transmission and Distribution, 1994