Reed Switch Overcurrent Protection: New Approach to Design
Authors:
- Dauren Dzhambulovich IssabekovDIDauren Dzhambulovich Issabekov
- Zhassulan Bakutzhanovich MussayevZMZhassulan Bakutzhanovich Mussayev
- Vadim Pavlovich MarkovskiyVMVadim Pavlovich Markovskiy
- Aleksandr Petrovich KislovAKAleksandr Petrovich Kislov
- Dariya Sansyzbayevna UrazalimovaDUDariya Sansyzbayevna Urazalimova
Open Access
Abstract
The problem of getting rid of expensive and metal-intensive current transformers has been declared by CIGRE as strategically important for the electric power industry. However, almost all traditional current protections receive information from measuring current transformers. In this work, a resource-saving reed switch overcurrent protection without current transformers is suggested, which can be used as an alternative to traditional current protections for 6–10 kV electrical installations connected to a switchgear cell. The protection is designed following the novel method we have developed based on inductance coils. Inductance coils measure the electromotive force under different operation modes of an electrical installation and at different points inside the switchgear cell it is connected to; the EMF values are recalculated in the values of magnetic induction, and reed switches are mounted instead of inductance coils at the points where the magnetic induction is maximal. Moreover, these values are sufficient to detect phase-to-phase short circuits in the electrical installation. The dependence of the induction value on the position of an inductance coil inside the cell is derived with the use of the simplest formula of the Biot–Savart law. The results can be used at large and small industrial enterprises, electric power stations, and substations of plants; they can be interesting for the scientific community because they help to solve the topical problem of the electric power industry.Keywords
Funding Information
- Committee on Science of the Ministry of Science and Higher Education of the Republic of Kazakhstan (AP14972954)
This publication has 12 references indexed in Scilit:
- The development of the soderberg electrolyzer electromagnetic field’s state monitoring systemScientific Reports, 2024
- Resource-saving protections of power transformers against internal faultsE3S Web of Conferences, 2023
- Multipurpose Power System Protection Set that Provides Constant Remote Serviceability Control2022
- Resilient protection scheme preserving system integrity during stressed conditionIET Generation, Transmission & Distribution, 2019
- Influence of electromagnetic forces in the gaps of a protective CTIET Science, Measurement & Technology, 2018
- New filters for symetrical current componentsInternational Journal of Electrical Power & Energy Systems, 2018
- Interference‐rejecting current measurement method with tunnel magnetoresistive magnetic sensor arrayIET Science, Measurement & Technology, 2018
- Optimal allocation of fault current limiters for sustaining overcurrent relays coordination in a power system with distributed generationAlexandria Engineering Journal, 2015
- Novel optical current sensor for metering and protection in high power applicationsInstrumentation Science & Technology, 2015