Improvement of the differential busbar characteristic to avoid false operation during to CT saturation
Author:
- 1 October 2012
- journal article
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 6 (10) , 931-939
Abstract
The proposed technique is based on extracting the windowed wavelet transform of fault generated transients to distinguish between faults in a busbar protection zone from those outside the zone, particularly in case of early and severe current transformer (CT) saturation. Most given techniques are tending to block the differential measurement during the portion of the cycle that a current transformer is saturated. Some other techniques bring more meaning to the breakpoint settings of the operating characteristic. The traditional differential concept is based on the current magnitude for estimating the restraining and biasing values. The significant imbalance comes from the secondary current of a current transformer with a resistive burden which collapses to zero when saturation occurs and it remains at zero until the time when the next zero crossing would have occurred. The study describes a new technique with improved characteristic and the differential concept does not depend on the current magnitude. The wavelet transform (WT) depends on high frequencies of the faulted signal produced owing to CT saturation. The proposed WT is based on Mexican basis function that was found to be an excellent discriminant for identifying the fault signals during the CT saturation. The time and frequency information during saturation are obtained rather than the current magnitude.Keywords
This publication has 16 references indexed in Scilit:
- A New Wavelet Transform Based Busbar Protection2006
- High-speed differential busbar protection using wavelet-packet transformIEE Proceedings - Generation, Transmission and Distribution, 2005
- Considerations in applying power bus protection schemes to industrial and IPP systems2003
- A new algorithm for digital low-impedance protection of busbars2001
- Theory and practical performance of interlocked overcurrent busbar zone protection in distribution substations2001
- Application of wavelet transform in transient protection - case study: busbar protection2001
- A new method for protection zone selection in microprocessor-based bus relaysIEEE Transactions on Power Delivery, 2000
- A digital compensation method for improving current transformer accuracyIEEE Transactions on Power Delivery, 2000
- Digital bus-zone protectionIEEE Computer Applications in Power, 1993
- A Half Cycle Bus Differential Relay and its ApplicationIEEE Transactions on Power Apparatus and Systems, 1974