An Improved Phase-Locked-Loop Control with Alternative Damping Factors for VSC Connected to Weak AC System
Authors:
Open Access
- 1 January 2016
- journal article
- research article
- Published by Wiley in Journal of Control Science and Engineering
- Vol. 2016, 1-13
Abstract
The gains of phase-locked-loop (PLL) have significant impacts on the power transfer limits for the voltage source converter (VSC) connected to weak AC system. Therefore, in this paper, an improved PLL control, respectively, with alternative damping factors for rectifier and inverter is proposed. First, it is proved that the impedance angle of AC system has a great impact on the small-signal stability of the VSC system. With the same variation tendency of Thévenin equivalent resistance, the limits of power transmission are changing in opposite trends for rectifier and inverter. Second, the improved PLL with alternative damping factors is proposed based on the participation factor analysis. Third, the optimal damping factors of the improved PLL control for rectifier and inverter are calculated. Simulations and calculations validated the following three conclusions: (1) in rectifying operation, the equivalent system resistance has a negative impact on the stability of the system and this is not the case for inverting operation; (2) adding the alternative damping factors to PLL control shows similar results compared with changing the impedance angle of AC system; (3) the proposed optimal damping factors of PLL can effectively extend the power transfer limits under both rectifier and inverter modes.Keywords
Funding Information
- National High Technology Research and Development Program of China (2013AA050105, 2015XS23, 2015QN04, 51177042)
- Fundamental Research Funds for the Central Universities (2013AA050105, 2015XS23, 2015QN04, 51177042)
- Fundamental Research Funds for the Central Universities (2013AA050105, 2015XS23, 2015QN04, 51177042)
- National Natural Science Foundation of China (2013AA050105, 2015XS23, 2015QN04, 51177042)
This publication has 13 references indexed in Scilit:
- Identification and Small-Signal Analysis of Interaction Modes in VSC MTDC SystemsIEEE Transactions on Power Delivery, 2015
- Analysis of D-Q Small-Signal Impedance of Grid-Tied InvertersIEEE Transactions on Power Electronics, 2015
- Advanced Vector Control for Voltage Source Converters Connected to Weak GridsIEEE Transactions on Power Systems, 2015
- Impedance and Damping Characteristics of Grid-Connected VSCs With Power Synchronization Control StrategyIEEE Transactions on Power Systems, 2014
- Impact of Short-Circuit Ratio and Phase-Locked-Loop Parameters on the Small-Signal Behavior of a VSC-HVDC ConverterIEEE Transactions on Power Delivery, 2014
- Adaptive Control of Grid-Connected Inverters Based on Online Grid Impedance MeasurementsIEEE Transactions on Sustainable Energy, 2014
- Small Signal Model for VSC-HVDC Connected DFIG-Based Offshore Wind FarmsJournal of Applied Mathematics, 2014
- Power-Synchronization Control of Grid-Connected Voltage-Source ConvertersIEEE Transactions on Power Systems, 2009
- Small signal stability analysis and optimal control of a wind turbine with doubly fed induction generatorIET Generation, Transmission & Distribution, 2007
- Phase-locked loop techniques. A surveyIEEE Transactions on Industrial Electronics, 1996