Indoor Air Quality Measurements in the Chemistry Department Building of the University of Athens
- 1 December 2006
- journal article
- research article
- Published by SAGE Publications in Indoor and Built Environment
- Vol. 15 (6) , 595-605
Abstract
This paper summarises results from 3 years of measurements in the building of the Chemistry Department of the University of Athens, Greece, focusing mainly on the undergraduate and postgraduate laboratories. We measured levels of carbon dioxide (CO2), carbon monoxide (CO), sulphur dioxide (SO2), nitrogen dioxide (NO2), chlorine (Cl2), formaldehyde (HCHO), ozone (O3), total volatile organic compounds (TVOC), total respirable suspended particulate matter (TSP), settled dust, temperature, relative humidity and noise in representative areas including laboratories, classrooms and offices. A questionnaire survey was conducted for complaints, working conditions and perception of indoor air quality. Our results showed that levels of air pollutants (especially CO2 and CO) were below the guidelines for upper limits (2) under normal conditions. Fume hoods were used but are adequate only for odoriferous and volatile chemicals in the restricted area of their enclosure. In some research laboratories, levels of formaldehyde were found in the range of 0.1-0.3ppm and TVOCs levels in the range of 4-8ppm. Concentrations of TSP in some laboratories were in the range of 0.1-0.7mg·m 3. Measurements in classrooms, amphitheatres and offices showed only the presence of air pollutants from human activities. Smoking was the main source of pollution in offices.Keywords
This publication has 23 references indexed in Scilit:
- Elemental carbon and respirable particulate matter in the indoor air of apartments and nursery schools and ambient air in Berlin (Germany)Indoor Air, 2005
- Relationship between outdoor and indoor air quality in eight French schoolsIndoor Air, 2004
- Determination of Selected Pollutants and Measurement of Physical Parameters for the Evaluation of Indoor Air Quality in School Buildings in Athens, GreeceIndoor and Built Environment, 2001
- HEALTH AND PRODUCTIVITY GAINS FROM BETTER INDOOR ENVIRONMENTS AND THEIR RELATIONSHIP WITH BUILDING ENERGY EFFICIENCYAnnual Review of Energy and the Environment, 2000
- Penetration of Nitrogen Oxides and Particles from Outdoor into Indoor Air and Removal of the Pollutants through Filtration of Incoming AirIndoor Air, 2000
- Total Volatile Organic Compounds (TVOC) in Indoor Air Quality Investigations*Indoor Air, 1997
- Relationships Between Ventilation and Indoor Air Quality: A ReviewIndoor Air, 1996
- Individual and Occupational Correlates of the Sick Building SyndromeIndoor Air, 1995
- Effects of Indoor Air Pollution on Human HealthIndoor Air, 1992
- Volatile Organic Compounds, Indoor Air Quality and HealthIndoor Air, 1991