Nanosecond switching transients recorded in a mining transformer installation
Authors:
- A.M. KunjiAKA.M. Kunji
- 1 July 1993
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 8 (3) , 1130-1137
Abstract
Tests carried out on a mining power transformer supply system to determine the severity of the switching transients developed with a range of system and plant conditions are described. Results obtained with vacuum and SF/sub 6/ circuit breakers are presented and indicate that very fast transients with wavefront durations as short as 10 ns are frequently produced. An examination of the transients is made, and the system and plant parameters that lead to the production of very fast transients are identified. Wavefront duration is mainly governed by system parameters and wave amplitude by the type of circuit breaker. The relevance of the results to other types of power transformer supply systems is indicated.Keywords
This publication has 4 references indexed in Scilit:
- Distribution transformer performance when subjected to steep front impulsesIEEE Transactions on Power Delivery, 1990
- Factors governing the severity of prestriking transients in motor systemsIEE Proceedings B Electric Power Applications, 1990
- Steep Front Short Duration Low Voltage Impulse Performance of Distribution TransformersIEEE Transactions on Power Delivery, 1987
- Surge Arrester Protection and Very Fast SurgesIEEE Transactions on Power Apparatus and Systems, 1983