Design limitations on a thermal siphon 4 K helium loop for cooling-down the cyclotron gas stopper magnet coils

Authors:

Abstract
The two Cyclotron gas stopper superconducting solenoid coils will be kept cold at 4.25 to 4.6 K using three pulse tube coolers per coil. These coolers are designed to produce from 1.35 to 1.6 W per cooler when the cooler first stage is at about 45 K. The cyclotron gas stopper coils are designed so that they can be separated while cold, but unpowered. This design decision means that the coils can be kept cold while maintenance is performed on the cyclotron. MSU decided that the cyclotron gas stopper would be cooled down from 300 K to 4 K using the coolers connected to the coils using a thermal-siphon cooling loop. This decision was in part influenced by the decision to have the solenoid axis perpendicular to the direction of the gravitational acceleration. The heat exchangers connected to the cooler cold heads must be above the top of the magnet coil. Cold gas from the cooler heat exchanger must enter the bottom of the magnet cryostat. The report describes the effect of the direction of gravitational acceleration with respect to the solenoid axis and other effects that will limit the cooling and cool-down of a magnet like the MSU cyclotron gas stopper magnet.