Central business district (CBD) hospitals must sustain reliable pressure relationships in critical rooms while reducing whole-facility carbon under tight space and disruption constraints. We developed an ontology-grounded semantic digital twin that normalizes building automation system (BAS) and building management system (BMS) telemetry into a unified semantic store consistent with Brick Schema, enabling portable asset discovery via query and thereby supporting forecasting, anomaly detection, and multi-objective optimization without dependence on vendor point naming conventions. Whole-facility impacts were verified using International Performance Measurement and Verification Protocol Option C–style measurement and verification with an S0-calibrated baseline model and residual-based savings attribution. Relative to the baseline (S0), the intervention (S3) produced a step increase in the critical-room pressure-compliance pass rate, tighter room-to-corridor differential-pressure (ΔP) control across airborne infection isolation and open room strata, and intent-aligned ventilation delivery (air changes per hour ratio distribution concentrated near unity; p < 0.05 where letter groups differ). Operational-state discrimination improved (AUC 0.649→0.696) and issue-resolution times shortened (left-shifted cumulative distribution function), indicating reduced service burden. Option C verification showed energy residuals shifting negative under S3, consistent with net savings versus baseline expectations. Across progressive maturity (S0→S3), time-to-value and burden fractions decreased, carbon intensity (tCO2e m−2) decreased, long-tail exposure compressed (log-scale horizon), and composite performance indices increased (p < 0.05). These results demonstrate a verifiable pathway to pressure-reliable, decarbonized hospital operations at the whole-facility boundary while making the semantic layer’s utility explicit through query-driven, ontology-grounded asset discovery. We present an IPMVP Option-C–verifiable semantic digital-twin governance framework that links audited operational evidence (telemetry → actions → verification) to whole-facility energy and carbon outcomes while maintaining critical-room pressure-relationship reliability. Optimization benchmarking (including quantum annealing) is used as supporting decision-support evaluation, rather than as the central contribution.

This publication has 39 references indexed in Scilit: