Abstract
The paper describes a theoretical investigation for the steady-state counter flow wet cooling tower with modified definitions for both the number of transfer units and the tower thermal effectiveness. The modified number of transfer units is dependent on both air and water heat capacity. The effectiveness is defined by the tower cooling range and the approach to equilibrium. A new expression relating the tower effectiveness to the modified number of transfer units and the capacity rate ratio has been developed. The model considered the resistance to heat transfer in the water film, the nonunity of the Lewis number, and the curvature of the saturated air enthalpy curve. A procedure for implementing the model in designing or rating cooling towers has been outlined and demonstrated through illustrative examples. The model compares very satisfactorily with other methods such as Logarithmic Mean Enthalpy Difference (LMED) and conventional effectiveness—NTU. Within the ranges used, the obtained results showed that substantial errors varied from +4.289 to −2.536 percent can occur in calculating the cooled water outlet temperature, and errors from +42.847 to −16.667 percent can occur in estimating the tower thermal characteristics.Keywords
This publication has 15 references indexed in Scilit:
- Thermal and hydraulic performance of a three-phase fluidized bed cooling towerExperimental Thermal and Fluid Science, 1993
- Design of Cooling Towers by the Effectiveness-NTU MethodJournal of Heat Transfer, 1989
- An effectiveness model of liquid-desiccant system heat/mass exchangersSolar Energy, 1989
- Numerical Modeling of Wet Cooling Towers—Part 1: Mathematical and Physical ModelsJournal of Heat Transfer, 1983
- Analysis of Mechanical-Draught Counterflow Air/Water Cooling TowersJournal of Heat Transfer, 1983
- A General Theory of Wet Surface Heat Exchangers and its Application to Regenerative Evaporative CoolingJournal of Heat Transfer, 1981
- The effect of evaporation losses in the analysis of counterflow cooling towersNuclear Engineering and Design, 1975
- Prediction of breakthrough curves in packed beds: I. Applicability of single parameter modelsAIChE Journal, 1972
- Prediction of breakthrough curves in packed beds: II. Experimental evidence for axial dispersion and intraparticle effectsAIChE Journal, 1972
- ADIABATIC GAS ABSORPTION AND STRIPPING IN PACKED TOWERSIndustrial & Engineering Chemistry, 1969