Synthesis and Evaluation of Fast Onload Multitap Changers for Flicker Compensation in AC Arc Furnaces
- 10 September 2014
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 29 (6) , 2519-2527
Abstract
This paper evaluates the abilities of fast tap-changer topologies by using insulated-gate bipolar transistors to mitigate flicker generated by the ac electric arc furnaces, based on technical and economic criteria. The design problems derived from the very high powers and currents involved have been solved to a preliminary industrial level. The operation of the best resulting topology is verified on a real 80-MVA arc furnace with a dedicated graphical-mathematical multilevel simulator developed to perform short- and long-term tests. Selected pattern windows of the arc voltage, taken from exhaustive logs of electric variables of a real 80-MVA furnace during a complete meltdown process, have been loaded into the simulator. This novel simulation strategy enables the testing of the proposed compensator under reproduced “real working conditions” with several degrees of flicker severity. The simulator includes an IEC flicker meter capable of checking the flicker level online at any point in the installation. The simple open-loop and closed-loop control tests confirm the new tap changer as a fast and economical competitor to other arc furnace compensators. It manages 16% of the furnace system power at a subcycle or supercycle tap changing rate (between 0 and 10 changes per half cycle), as required. This fast switching capacity reduces the compensating time to the very limited values imposed by the L/R time constant of the furnace installation.Keywords
This publication has 14 references indexed in Scilit:
- The Effect of Wind Power Integration on the Frequency of Tap Changes of a Substation TransformerIEEE Transactions on Power Systems, 2013
- STATCOM for flicker suppression from a steel plant connected to a weak 66 kV grid2010
- Analysis of Fast Onload Multitap-Changing Clamped-Hard-Switching AC StabilizersIEEE Transactions on Power Delivery, 2006
- Flicker mitigation with the Smarttrafo2005
- Power electronics simulation: current progress and future development2002
- Flicker Sources and MitigationIEEE Power Engineering Review, 2002
- Flicker analysis and methods for electric arc furnace flicker (EAF) mitigation (a survey)2002
- Optimal configurations for taps of windings and power electronic switches in electronic tap-changersIEE Proceedings - Generation, Transmission and Distribution, 2002
- Harmonics, interharmonics and unbalances of arc furnaces: a new frequency domain approachIEEE Transactions on Power Delivery, 2001
- Active power filters for line conditioning: a critical evaluationIEEE Transactions on Power Delivery, 2000