An Enhanced X Model of Oil-Impregnated Paper Bushings Including Axial and Radial Nonuniform Thermal Aging
- 9 December 2022
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Dielectrics and Electrical Insulation
- Vol. 30 (2) , 825-833
Abstract
The X model is a conventional tool of frequency domain spectroscopy (FDS) technology for assessing the insulation state of oil-impregnated paper (OIP) bushings. However, the accuracy and applicability of the X model are questionable because it overlooked the effect of non-uniform thermal ageing, and there are no models and mathematical formulas that can be applied to non-uniform thermal-aged OIP bushings. To solve this issue, an enhanced X model is proposed by considering the radial and axial non-uniform thermal ageing of OIP bushings. The enhanced X model’s mathematical formula was deduced initially. Then, the complex relative permittivity (CRP) of three types of non-uniform thermally aged OIP bushings was tested. Comparing the calculated CRP based on the enhanced X model to the laboratory-measured CRP reveals that the average relative error of the real part and imaginary part of the CRP are 7.24% and 10.94%, respectively, which indicates that the accuracy and practicability of the enhanced X model are good. It is anticipated that the contributions will provide a theoretical foundation for the state assessment of the OIP bushings under non-uniform thermal ageing.Keywords
Funding Information
- National Natural Science Foundation of China (51867003)
This publication has 25 references indexed in Scilit:
- Quantitative diagnosis of moisture content in oil‐paper condenser bushing insulation based on frequency domain spectroscopy and polarisation and depolarisation currentIET Generation, Transmission & Distribution, 2017
- Dielectric response measurement by impulse stimulus on AC: Measurement considerations, and laboratory testing on a bushingIEEE Transactions on Dielectrics and Electrical Insulation, 2017
- Detection of conductive layers short circuit in HV condenser bushings using Frequency Domain SpectroscopyIEEE Transactions on Dielectrics and Electrical Insulation, 2017
- Heat analysis of the power transformer bushings using the finite element methodApplied Thermal Engineering, 2016
- Study of the Impact of Initial Moisture Content in Oil Impregnated Insulation Paper on Thermal Aging Rate of Condenser BushingEnergies, 2015
- Explanation and analysis of oil-paper insulation based on frequency-domain dielectric spectroscopyIEEE Transactions on Dielectrics and Electrical Insulation, 2015
- A dielectric frequency response model to evaluate the moisture content within an oil impregnated paper condenser bushingIET Science, Measurement & Technology, 2013
- Dielectric spectroscopic measurements on transformer oil-paper insulation under controlled laboratory conditionsIEEE Transactions on Dielectrics and Electrical Insulation, 2008
- Frequency Response of Oil Impregnated Pressboard and Paper Samples for Estimating Moisture in Transformer InsulationIEEE Transactions on Power Delivery, 2006
- Aging of Oil-Impregnated Paper in Power TransformersIEEE Transactions on Power Delivery, 2004