Fault identification of power transformers using genetic-based wavelet networks
Author:
- 6 January 2003
- journal article
- Published by Institution of Engineering and Technology (IET) in IEE Proceedings - Science, Measurement and Technology
- Vol. 150 (1) , 25-29
Abstract
The paper presents genetic-based wavelet networks (GWNs) for fault identification of power transformers. GWNs are three-layer structures, which contain wavelet, weighting and summing layers. Using a genetic-algorithm (GA) based optimisation process, the GWNs automatically tune the network parameters, translation and dilation in the wavelet nodes and the weighting values in the weighting nodes. The GWNs, with global search abilities of the GA and the multiresolution and localisation natures of the wavelets, can identify the complicated relations of dissolved gas contents in transformer oil to corresponding fault types. The proposed GWNs have been tested on the Taipower Company diagnostic records and compared with the fuzzy diagnosis system, artificial neural networks as well as the conventional method. The experimental results reveal that the GWNs have remarkable diagnostic accuracy and require far less construction time than conventional methods.Keywords
This publication has 20 references indexed in Scilit:
- Degradation of cellulosic insulationin power transformers.Part 4: Effects of ageing on the tensile strength of paperIEE Proceedings - Science, Measurement and Technology, 2000
- Degradation of cellulosic insulationin power transformers. Part2: Formation of furan products in insulating oilIEE Proceedings - Science, Measurement and Technology, 2000
- Degradation of cellulosic insulationin power transformers.Part 3: Effects of oxygen and water on ageing in oilIEE Proceedings - Science, Measurement and Technology, 2000
- Degradation of cellulosic insulationin power transformers.Part 1: Factors affecting the measurement of the average viscometric degree ofpolymerisation of new and aged electrical papersIEE Proceedings - Science, Measurement and Technology, 2000
- Adaptive fuzzy diagnosis system for dissolved gas analysis of power transformersIEEE Transactions on Power Delivery, 1999
- Developing a new transformer fault diagnosis system through evolutionary fuzzy logicIEEE Transactions on Power Delivery, 1997
- An expert system for transformer fault diagnosis using dissolved gas analysisIEEE Transactions on Power Delivery, 1993
- Dissolved gas analysis: It can save your transformerIEEE Electrical Insulation Magazine, 1989
- Transformer Fault Diagnosis by Dissolved-Gas AnalysisIEEE Transactions on Industry Applications, 1980
- IEEE and IEC Codes to Interpret Incipient Faults in Transformers, Using Gas in Oil AnalysisIEEE Transactions on Electrical Insulation, 1978