Investigation of electrical tree propagation from water tree by utilizing partial discharge and optical observation
Authors:
- K. WuKWK. Wu
- F. KomoriFKF. Komori
- Y. SuzuokiYSY. Suzuoki
- 13 May 2004
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- Vol. 3 (10817735) , 891-894
Abstract
In order to clarify the mechanism of electrical tree propagation from a water tree within polyethylene, we have carried out simultaneous observation of partial discharge (PD) characteristics, electrical-tree propagation and associated phenomena. The electrical tree inception voltage increases with the area of water tree degradation. An electrical tree is initiated from a water needle tip. When the electrical tree connects with water needle, PDs become large abruptly. There are two types of electrical-tree growth, in one of which only small PDs occur only at the electrical-tree tips. After removing the applied voltage, water fills the electrical-tree channels, and water trees propagate from the electrical-tree tips when the voltage is applied again.Keywords
This publication has 2 references indexed in Scilit:
- Model for partial discharges associated with treeing breakdown: III. PD extinction and re-growth of treeJournal of Physics D: Applied Physics, 2000
- Comparison between water-treed and deteriorated regions. Electrical tree precursorIEEE Transactions on Dielectrics and Electrical Insulation, 1994