Parameters affecting the arcing time of HVDC circuit breakers using black box arc model
Open Access
- 18 January 2019
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 13 (4) , 461-467
Abstract
Arc interruption of high voltage direct current (HVDC) circuit breakers (CBs) is one of the main challenging factors for using HVDC grids. To evaluate the arc interrupting capability in HVDC CBs, black box arc models are used to represent the nonlinear arc conductance depending on Cassie and Mayr dynamic arc equations. Extensive simulation studies are carried out to investigate the effect of controlled and uncontrolled parameters on the CB arcing time. A real line represents a part of 500 kV electrical connection systems between Egypt and the Kingdom of Saudi Arabia is simulated to be a faulty load. It is found that the arcing time of the HVDC CB can be reduced by increasing the value of cooling power coefficient ( p ) and decreasing the value of arc time constant ( τ ). It is also deduced that the arcing time is reduced by the increase of the commutation capacitance value ( C ) and decreasing the commutation inductance ( L ) value and vice versa. Moreover, it is concluded that the arcing time is greatly affected by the fault location and the fault arc resistance ( ) according to fault conditions.Keywords
This publication has 30 references indexed in Scilit:
- Study of the switching arc characteristics of a 500 kV HVDC self-excited oscillatory metallic return transfer breakerIEEE Transactions on Dielectrics and Electrical Insulation, 2015
- Multi-terminal VSC-HVDC Pole-to-pole Fault Analysis and Fault Recovery Study2015
- Research on the control method for voltage-current source hybrid-HVDC systemScience China Technological Sciences, 2013
- Optimizing HVDC control parameters in multi-infeed HVDC system based on electromagnetic transient analysisInternational Journal of Electrical Power & Energy Systems, 2013
- Optimal acquisition and aggregation of offshore wind power by multiterminal voltage-source HVDCIEEE Transactions on Power Delivery, 2003
- HVDC transmission for large offshore wind farmsPower Engineering Journal, 2002
- DC current interruption in HVDC SF/sub 6/ gas MRTB by means of self-excited oscillation superimpositionIEEE Transactions on Power Delivery, 2001
- Simulation of arc-circuit instability in a low current DC automotive switching applicationIEEE Transactions on Vehicular Technology, 1995
- The Corsican tapping: from design to commissioning tests of the third terminal of the Sardinia-Corsica-Italy HVDCIEEE Transactions on Power Delivery, 1989
- Development of a high current HVDC circuit breaker with fast fault clearing capabilityIEEE Transactions on Power Delivery, 1988