Combination Optimization Configuration Method of Capacitance and Resistance Devices for Suppressing DC Bias in Transformers
Open Access
Abstract
The ground current of a high-voltage direct current (HVDC) transmission system can cause DC bias in transformers near the grounding electrode during monopole operations, which affects the alternating current (AC) power system operation. Owing to multiple bias current flow paths, a capacitance blocking device installed at the neutral point of a transformer may increase the DC bias in adjacent transformers, while suppressing the DC current in that transformer. This paper introduces the use of an effective bias current indicator to describe the effect of the grounding current on transformers in a network, considering the wiring characteristics of the autotransformers and the power system topology. Additionally, a combination optimization method for the capacitance and resistance is applied in order to determine the minimum number of installed devices that restrict the maximum effective bias current throughout the network to a permissible range. A genetic algorithm based on an improved roulette selection method is adopted to solve the optimal configuration problem. The method is validated by using a test case based on the Xizhe HVDC transmission receiving-end grid near the Jinsi grounding electrode. The configuration of the capacitance and resistance was optimized by the improved genetic algorithm. This method can achieve the desired level of DC bias management with fewer devices than the conventional method, which verifies the feasibility and superiority of the proposed optimization method.Keywords
Funding Information
- National Key R&D Program of China (2016YFC0800100)
This publication has 27 references indexed in Scilit:
- Research on DC bias analysis for transformer based on vibration Hilbert Huang transform and ground-state energy ratio methodInternational Journal of Electrical Power & Energy Systems, 2019
- Vibration characteristic investigation on distribution transformer influenced by DC magnetic bias based on motion transmission modelInternational Journal of Electrical Power & Energy Systems, 2018
- Influence of Deep Earth Resistivity on HVDC Ground-Return Currents DistributionIEEE Transactions on Power Delivery, 2016
- High-Wire Act: HVdc Technology: The State of the ArtIEEE Power and Energy Magazine, 2012
- Vibration and Audible Noise Characteristics of AC Transformer Caused by HVDC System Under Monopole OperationIEEE Transactions on Power Delivery, 2012
- HVDC Circuit Breakers: A Review Identifying Future Research NeedsIEEE Transactions on Power Delivery, 2011
- Geomagnetically Induced Currents in the High-Voltage Power Grid in ChinaIEEE Transactions on Power Delivery, 2009
- Numerical Analysis of DC Current Distribution in AC Power System Near HVDC SystemIEEE Transactions on Power Delivery, 2008
- Calculation of DC current distribution in AC power system near HVDC system by using moment method coupled to circuit equationsIEEE Transactions on Magnetics, 2006
- Measurement of magnetostriction and vibration with regard to transformer noiseIEEE Transactions on Magnetics, 1974