Application of Detectability Analysis for Power System Dynamic State Estimation
- 15 April 2020
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Systems
- Vol. 35 (4) , 3274-3277
Abstract
In this paper, detectability analysis is studied and extended to guide selection of measurements for the dynamic state estimation (DSE) of a synchronous machine. To make sure that the DSE converges, past studies suggested that enough measurements must be available to make the system observable. In this paper, the convergence condition is relaxed via detectability analysis to reduce the number of required measurements. Because the objective of the DSE is to estimate the current states as time progresses, it is shown that a DSE observer can converge not only for an observable system but also for an unobservable system if the eigenvalues corresponding to the unobservable states are stable. Simulation results using the IEEE 10-machine, 39-bus system show that the unscented-Kalman-filter-based DSE can converge when measurements are chosen such that the unobservable states have stable eigenvalues. In comparison with observability analysis, the proposed application of detectability analysis can reduce the number of measurements required for the existence of a DSE observer.Keywords
Funding Information
- U.S. Department of Energy (1845523)
- NSF (1845523)
- Pacific Northwest National Laboratory (DE-AC05-76RL01830)
This publication has 10 references indexed in Scilit:
- A New Multi-Scale State Estimation Framework for the Next Generation of Power Grid EMS2019
- Power System Dynamic State Estimation: Motivations, Definitions, Methodologies, and Future WorkIEEE Transactions on Power Systems, 2019
- Robust Unscented Kalman Filter for Power System Dynamic State Estimation With Unknown Noise StatisticsIEEE Transactions on Smart Grid, 2017
- Observability Analysis for Dynamic State Estimation of Synchronous MachinesIEEE Transactions on Power Systems, 2016
- Power system observability and dynamic state estimation for stability monitoring using synchrophasor measurementsControl Engineering Practice, 2016
- Benchmark Models for the Analysis and Control of Small-Signal Oscillatory Dynamics in Power SystemsIEEE Transactions on Power Systems, 2016
- Optimal PMU Placement for Power System Dynamic State Estimation by Using Empirical Observability GramianIEEE Transactions on Power Systems, 2014
- Filtering and System Identification2007
- Power System Stability: New Opportunities for Control2003
- Robust pole assignment in linear state feedbackInternational Journal of Control, 1985