UHF partial discharge localisation method in substation based on dimension‐reduced RSSI fingerprint
Authors:
Open Access
- 27 October 2017
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 12 (2) , 398-405
Abstract
Ultra‐high frequency (UHF) technique is chosen for partial discharge (PD) detection due to its excellent anti‐interference and stability. The existing UHF PD localisation methods are mainly based on time‐difference technique, that suffer high hardware cost due to the high sampling rate requirement. The wireless UHF sensors together with the scene analysis methods, i.e. received signal strength indicator (RSSI) fingerprint, provide us a low hardware cost and high environmental adaptability solution for PD localisation in substation. The proposed PD localisation method here is divided into two stages. In the offline stage, the RSSI fingerprint map is established by site survey. In the online stage, the position of PD source is estimated by a probabilistic approach. To reduce the influence of noise, the RSSI fingerprints are transformed to a low‐dimensional subspace, while the most of redundant noise is discarded. Furthermore, the PD heterogeneity and interference in the offline stage are also discussed and solved by normalisation and clustering algorithm, respectively. A filed test is performed and the results indicate that the mean localisation error is 1.87 m and 82.6% localisation errors are <3 m. The workload in the offline stage is also reduced ∼50%.Keywords
This publication has 25 references indexed in Scilit:
- A semi-definite relaxation approach for partial discharge source location in transformersIEEE Transactions on Dielectrics and Electrical Insulation, 2015
- Advancing new techniques for UHF PDdetection and localization in the power transformers in the factory testsIEEE Transactions on Dielectrics and Electrical Insulation, 2015
- Robust Time Delay Estimation Method for Locating UHF Signals of Partial Discharge in SubstationIEEE Transactions on Power Delivery, 2013
- Comprehensive Operational Planning Framework for Self-Healing Control Actions in Smart Distribution GridsIEEE Transactions on Power Systems, 2013
- A Perturbation Analysis on the Performance of TOA and TDOA Localization in Mixed LOS/NLOS EnvironmentsIEEE Transactions on Communications, 2013
- Partial discharge localization in transformers using UHF detection methodIEEE Transactions on Dielectrics and Electrical Insulation, 2012
- Environmental-adaptive indoor radio path loss model for wireless sensor networks localizationAEU - International Journal of Electronics and Communications, 2011
- RF-Based Partial Discharge Early Warning System for Air-Insulated SubstationsIEEE Transactions on Power Delivery, 2008
- Principal Component and Hierarchical Cluster Analyses as Applied to Transformer Partial Discharge Data With Particular Reference to Transformer Condition MonitoringIEEE Transactions on Power Delivery, 2008
- Robustness of TOA and TDOA Positioning Under Suboptimal Weighting ConditionsIEEE Transactions on Aerospace and Electronic Systems, 2007