Probabilistic Prognostics and Health Management of Power Transformers Using Dissolved Gas Analysis Sensor Data and Duval’s Polygons
Open Access
Abstract
Power transformers are critical assets in modern power grids, where failures can lead to significant operational disruptions and financial losses. Dissolved Gas Analysis (DGA) is a key sensor-based technique widely used for condition monitoring, but traditional diagnostic approaches rely on deterministic thresholds that overlook uncertainty in degradation dynamics. This paper proposes a probabilistic framework for Prognostics and Health Management (PHM) of power transformers, integrating self-adaptive Auto Regressive Integrated Moving Average modeling with a probabilistic reformulation of Duval’s graphical methods. The framework enables automated estimation of fault types and failure likelihood directly from DGA sensor data, without requiring labeled datasets or expert-defined rules. Dissolved gas dynamics are forecasted using time-series models with residual-based uncertainty quantification, allowing probabilistic fault inference from predicted gas trends without assuming deterministic persistence of a specific fault type. A sequential pipeline is developed for real-time fault tracking and reliability assessment, aligned with IEC, IEEE, and CIGRE standards. Two case studies validate the method: one involving gas loss in an experimental setup and another examining thermal degradation in a 345 kV transformer. Results show that the framework improves diagnostic reliability, supports early fault detection, and enhances predictive maintenance strategies. By combining probabilistic modeling, time-series forecasting, and sensor-based diagnostic inference, this work contributes a practical and interpretable PHM solution for sensor-enabled monitoring environments in modern power grids.Keywords
Funding Information
- Fundação para o Desenvolvimento Tecnológico da Engenharia
- Conselho Nacional de Desenvolvimento Científico e Tecnológico (303986/2022-0)
- EDP Brasil for the development of the present research as part of an ANEEL R&D Project
This publication has 73 references indexed in Scilit:
- Machine learning based multi-method interpretation to enhance dissolved gas analysis for power transformer fault diagnosisHeliyon, 2024
- Conventional methods of dissolved gas analysis using oil-immersed power transformer for fault diagnosis: A reviewElectric Power Systems Research, 2022
- Prediction of dissolved gas concentration in transformer oil considering data loss scenarios in power systemEnergy Reports, 2022
- Prediction of the dissolved gas concentration in power transformer oil based on SARIMA modelEnergy Reports, 2022
- Online dissolved gas analysis used for transformers – possibilities, experiences, and limitationse+i Elektrotechnik und Informationstechnik, 2022
- An Analysis of Power Transformer Outages and Reliability MonitoringEnergy Procedia, 2017
- Lithium-ion batteries remaining useful life prediction based on a mixture of empirical mode decomposition and ARIMA modelMicroelectronics Reliability, 2016
- Distribution transformers failures: How does it cost? Evidence from GreeceEnergy Systems, 2016
- Integrated power transformer diagnosis using hybrid fuzzy dissolved gas analysisIEEJ Transactions on Electrical and Electronic Engineering, 2015