Steady-state invariant frequency and amplitude droop control using adaptive output impedance for parallel-connected UPS inverters
Authors:
- J.M. GuerreroJ.M. Guerrero
- L.G. de VicunaLVL.G. de Vicuna
- J. MatasJ. Matas
- J. MiretJMJ. Miret
- J. CruzJCJ. Cruz
- 28 June 2005
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- Vol. 1 (10482334) , 560-566
Abstract
In this paper, a novel wireless load-sharing controller for parallel connected UPS inverters is proposed. As opposed to the conventional droop method, the proposed method achieves stable steady-state frequency and amplitude. The paper explorers the output impedance of the UPS inverters, and adaptive virtual output impedance is proposed in order to reduce its line impedance impact. Experimental results are presented from two 6 kVA UPS inverters controlled by TMS320LF2407A DSP boards, showing the feasibility of the proposed approachKeywords
This publication has 17 references indexed in Scilit:
- Circulating current's characteristics analysis and the control strategy of parallel system based on double close-loop controlled VSI2004
- Repetitive-Based Control for Selective Harmonic Compensation in Active Power FiltersIEEE Transactions on Industrial Electronics, 2004
- A Wireless Controller to Enhance Dynamic Performance of Parallel Inverters in Distributed Generation SystemsIEEE Transactions on Power Electronics, 2004
- Uninterruptible power supplies: classification, operation, dynamics, and control2003
- Small signal stability for single phase inverter connected to stiff AC system2003
- Novel architectures and control for distributed UPS systems2002
- A simple method for parallel operation of inverters2002
- Parallel UPS with a instantaneous current sharing control2002
- A multimodule parallelable series-connected PWM voltage regulatorIEEE Transactions on Industrial Electronics, 2001
- Transmission power control using variable inductance with feedforward- and feedback-based power controllers1999