Faulty Phase Recognition Method for Single-Line-to-Ground Fault in Resonant Grounded Distribution Networks

Authors:
  • WWWen Wang
    Wen Wang
  • FWFaliang Wang
    Faliang Wang
  • XRXingqiang Ren
    Xingqiang Ren
  • ZWZhen Wang
    Zhen Wang

Abstract
Single-line-to-ground (SLG) faults account for a large proportion of faults in the distribution network. Because of the asymmetry of parameters in the actual operation of power grid, the traditional criterion based on strict symmetry of system parameters may fail. In order to find a more accurate SLG faulty phase judgment method, in this paper, by analyzing the zero-sequence voltage trajectory during over-compensation of SLG fault in distribution network, the variation rules of magnitude and phase angle of zero-sequence voltage changed with the increase of ground-fault conductance are obtained, and it is found that the distribution of the rules is related to the three-phase asymmetry ratio of the power grid. It is therefore proposed to identify the faulty phase by the correspondence between the three-phase asymmetry ratio and the zero-sequence voltage trajectory. The simulation proves that this method can accurately and quickly judge the faulty phase, especially for the SLG fault with high ground-fault resistance.

This publication has 2 references indexed in Scilit: