Abstract
Converter transformers play an important role in the high-voltage DC power transmission system. The insulation of these transformers is stressed by both AC and DC voltages. Particle contamination is one of the major problems in insulation structures, as they generate partial discharges. A methodical experimental study was carried out to understand the partial discharge formation because of single macroscopic conducting particle movement in transformer oil at different temperatures under DC voltages using ultra-high-frequency (UHF) technique. It is observed that the single particle moves in the vertical electrode gap under the DC voltage, and generates UHF signal in the range of 1–3 GHz. At high electric fields, the levitated particle sometime floats in the oil medium and as and when the applied voltage is removed, the particle slowly drops down. When it comes in contact with ground electrode, it generates UHF signals with the frequency content lying in the range of 1–3 GHz. Oil breakdown tests were carried out (without any particle in the oil electrode gap) under DC voltages and fast Fourier transform (FFT) analysis of the signal generated by the UHF sensor because of breakdown indicates that the frequency content of the UHF sensor signal lies up to 1 GHz.Keywords
This publication has 23 references indexed in Scilit:
- Influence of carbon particles on the breakdown voltage of transformer oil2002
- Charges and discharges of conducting particles in a plane oil gap subjected to a dc voltage2002
- A review of faults detectable by gas-in-oil analysis in transformersIEEE Electrical Insulation Magazine, 2002
- Modeling of conductive particle behavior in insulating fluids affected by DC electric fieldsIEEE Transactions on Industry Applications, 1998
- Partial discharge. XXI. Acoustic emission based PD source location in transformersIEEE Electrical Insulation Magazine, 1995
- Particle-initiated breakdown in a quasi-uniform field in transformer oilIEEE Transactions on Dielectrics and Electrical Insulation, 1995
- The movement of a conducting particle in transformer oil in AC fieldsIEEE Transactions on Electrical Insulation, 1993
- The measurement of charge on single particles in transformer oilIEEE Transactions on Electrical Insulation, 1991
- Recommended Dielectric Tests and Test Procedures for Converter Transformers and Smoothing ReactorsIEEE Transactions on Power Delivery, 1986
- Particle Contamination Levels in Oil-Filled Large Power TransformersIEEE Transactions on Power Apparatus and Systems, 1983