Lightning Performance of Transmission Lines: Requirements of Tower-Footing Electrodes Consisting of Long Counterpoise Wires
- 27 October 2015
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 31 (4) , 1524-1532
Abstract
This paper addresses the requirements of tower-footing electrodes for ensuring improved lightning performance of transmission lines. The response of typical arrangements of electrodes subjected to lightning currents is simulated using an electromagnetic model and their influent parameters are calculated. Simple expressions are provided for their estimation. Lightning overvoltages across insulators due to direct strikes to real lines are determined, and backflashover occurrence is assessed using the Disruptive Effect model. Concise representations of tower-footing electrodes are tested. Two original results ensued: 1) the ascertainment that the effective length of counterpoise wires is longer than that of horizontal and four-star electrodes and 2) the finding that using the impulse impedance for a concise representation of tower-footing electrodes in the assessment of the lightning performance of lines yields practically the same result obtained under their physical representation.Keywords
Funding Information
- FAPEMIG - The State of Minas Gerais Research Foundation (TEC APQ-02141-14)
This publication has 21 references indexed in Scilit:
- Lightning Response of Grounding Grids: Simulated and Experimental ResultsIEEE Transactions on Electromagnetic Compatibility, 2014
- The Response of Grounding Electrodes to Lightning Currents: The Effect of Frequency-Dependent Soil Resistivity and PermittivityIEEE Transactions on Electromagnetic Compatibility, 2011
- A Comprehensive Approach to the Grounding Response to Lightning CurrentsIEEE Transactions on Power Delivery, 2006
- HEM: A Model for Simulation of Lightning-Related Engineering ProblemsIEEE Transactions on Power Delivery, 2005
- Transient Voltages in Transmission Lines Caused by Direct Lightning StrikesIEEE Transactions on Power Delivery, 2005
- Effective Length of Counterpoise Wire Under Lightning CurrentIEEE Transactions on Power Delivery, 2005
- Performance of large air gaps under lightning overvoltages: experimental study and analysis of accuracy predetermination methodsIEEE Transactions on Power Delivery, 1989
- The generalized integration method for predicting impulse volt-time characteristics for non-standard wave shapes-a theoretical basisIEEE Transactions on Electrical Insulation, 1988
- A New Calculation Method of Breakdown Voltage-Time Characteristics of Long Air GapsIEEE Transactions on Power Apparatus and Systems, 1985
- Experimental study of breakdown voltage-time characteristics of large air gaps with lightning impulsesIEEE Transactions on Power Apparatus and Systems, 1977