Wavelet transform approach to distance protection of transmission lines
Authors:
- 1 January 2001
- conference paper
- Published by Institute of Electrical and Electronics Engineers (IEEE)
- Vol. 1, 115-120 vol.1
Abstract
An application of wavelet transform to digital distance protection for transmission lines is presented in this paper. Fault simulation is carried out using the Power System Computer Aided Design program (PSCAD). The simulation results are used as an input to the proposed wavelet transform protection-relaying technique. The technique is based on decomposing the voltage and current signals at the relay location using wavelet filter banks (WFB). From the decomposed signals, faults can be detected and classified. Also the fundamental voltage and current phasors, which are needed to calculate the impedance to the fault point can be estimated. Results demonstrate that wavelets have high potential in distance relaying.Keywords
This publication has 9 references indexed in Scilit:
- A novel technique for high impedance fault identificationIEEE Transactions on Power Delivery, 1998
- Artificial neural network approach to distance protection of transmission linesIEEE Transactions on Power Delivery, 1998
- Wavelet transform for high impedance fault identification1997
- Wavelets: a new tool for the resonant grounded power distribution systems relayingIEEE Transactions on Power Delivery, 1996
- Power quality assessment via wavelet transform analysisIEEE Transactions on Power Delivery, 1996
- Wavelets and electromagnetic power system transientsIEEE Transactions on Power Delivery, 1996
- Ten Lectures on Wavelets1992
- A theory for multiresolution signal decomposition: the wavelet representationIEEE Transactions on Pattern Analysis and Machine Intelligence, 1989
- Application of Kalman Filtering in Computer RelayingIEEE Transactions on Power Apparatus and Systems, 1981