Sub-Transmission Ground Fault Overvoltage Management Under IBR Reverse Flow
- 4 June 2024
- journal article
- research article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Delivery
- Vol. 39 (4) , 2560-2562
Abstract
The rise of inverter-based distributed energy resources (IBRs) is reshaping global power system planning and operation. Unlike traditional rotating machines, IBRs lack physical characteristics and rely on control algorithms to support the grid during abnormal conditions. This is especially evident in mass-adopted distributed sources like rooftop residential-scale Distributed Energy Resources (DER), which are controlled to behave as constant current sources. Numerous jurisdictions already experience steady-state reverse flows at substations during periods of minimum load and maximum generation. However, the aggregation of IBRs exacerbates ground fault overvoltages (GFOV) at the transmission level, as they appear as open circuits in the zero and/or negative sequence networks. This paper analyzes the issue through electromagnetic transient (EMT) simulations, yielding chart-based screening guidelines. These guidelines can assist utilities in evaluating necessary retrofits for substations as more IBRs are adopted, particularly for small-scale IBRs that are interconnected with little to no rigorous analysis.Keywords
This publication has 7 references indexed in Scilit:
- Impact of IBR Negative-Sequence Current Injection on Ground Fault Temporary Overvoltage and Ground Overcurrent Protection2022
- IEEE Standard for Interconnection and Interoperability of Inverter-Based Resources (IBRs) Interconnecting with Associated Transmission Electric Power Systems2022
- Practical Charts for Sizing Neutral Grounding Elements for Machine-Based Distributed Energy Source Step-Up TransformersIEEE Transactions on Power Systems, 2022
- IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces--Amendment 1: To Provide More Flexibility for Adoption of Abnormal Operating Performance Category III2020
- IEEE Recommended Practice for System Grounding of Industrial and Commercial Power Systems2019
- Dynamic Analysis of Small Wind Turbines Frequency Support Capability in a Low-Power Wind-Diesel MicrogridIEEE Transactions on Industry Applications, 2017
- IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems--Part I: Introduction2017